Contact Information:
202 West 4th Street
Alturas, CA 96101-3915
(530) 233-6419
|
 |
|
 |
Modoc County Air Pollution Control District-CALIFORNIA
DE MINIMIS EXEMPTIONS (Must Meet 1298):
None.
MINOR SOURCE PERMITTING:
The district has never permitted a minor source electric generating facility. There are no specific rules established,
but the district would require BACT based on CARB's guidance. Sample BACT for control of NOx from turbines and internal combustion
engines is as follows:
| Size of Unit |
Level of Control (ppm) |
| >3 MW |
9 |
| 3-12 MW simple cycle |
2.5 |
| 3-12 MW combined cycle |
5 |
| 12-50 MW simple cycle |
2.5 |
| 12-50 MW combined cycle |
5 |
| IC Engines |
9 |
TREATMENT OF EMERGENCY ENGINES:
An emergency engine would likely be exempted from permitting, but no requirements have been established.
 |
|
 |